Function library lenzedrive.lib, Special functions – Lenze DDS Function library Drive User Manual

Page 91

Advertising
background image

Function library LenzeDrive.lib

Special functions

2.7.5

Process controller (L_PCTRL)

2−81

L

LenzeDrive.lib EN 1.7

Gain V

p

The gain V

p

can be set in different ways. By using byPCharacteristic you can select the function you

require.

With nActVp you can display the actual value of the gain V

p

.

byPCharacteristic = 0:

·

The gain V

p

is provided by nVp.

byPCharacteristic = 1:

0

100%

nAdapt_a

V

p

nV

p

nV

p2Adapt

Fig. 2−76

The gain V

p

is provided by nAdapt_a

·

The gain V

p

is provided by nAdapt_a. The input value is led via a linear characteristic. The

slope of the characteristic is fixed by nVp(upper limit) and nVp2Adapt (lower limit). The value in
nVp is valid if the input value = +100 % or −100 % (100 % = 16384). The value in nVp2Adapt is
valid if the input value = 0.

byPCharacteristic = 2:

V

p

nV

p

nV

p2Adapt

nV

p3Adapt

nSet_a

nSet1Adapt

nSet2Adapt

Fig. 2−77

The gain V

p

derived from the process setpoint nSet_a

·

The gain V

p

is derived from the process setpoint nSet_a. The setpoint is acquired after the

ramp generator, and calculated from a characteristic with 3 interpolation points.

byPCharacteristic = 3:

·

The gain V

p

is derived from the control difference, and led by the same characteristic

generation as for byPCharacteristic = 2.