14 ramp generator (l_rfg), Ramp generator (l_rfg), Function library lenzedrive.lib – Lenze DDS Function library Drive User Manual

Page 34: Analog signal processing

Advertising
background image

2.2.14

Ramp generator (L_RFG)

Function library LenzeDrive.lib

Analog signal processing

2−24

L

LenzeDrive.lib EN 1.7

2.2.14

Ramp generator (L_RFG)

This FB functions as a ramp generator to control the rate of rise of signals.

L _ R F G

n I n _ a

n O u t _ a

d n T i r

0

1

n S e t _ a

b L o a d _ b

d n T i f

Fig. 2−26

Ramp generator (L_RFG)

VariableName

DataType

SignalType

VariableType

Note

nIn_a

Integer

analog/velocity

VAR_INPUT

nSet_a

Integer

analog/velocity

VAR_INPUT

bLoad_b

Boo

binary

VAR_INPUT

nOut_a

Integer

analog/velocity

VAR_OUTPUT

dnTir

Double Integer

VAR CONSTANT RETAIN

Acceleration time T

ir

dnTif

Double Integer

VAR CONSTANT RETAIN

Deceleration time T

if

Parameter codes of the instances

Variable name

L_RFG1

SettingRange

Lenze

dnTir

C0671

0.000 ... 999.999 s

0.000

dnTif

C0672

0.000 ... 999.999 s

0.000

Range of functions

·

Calculation and setting of the acceleration and deceleration times

·

Loading of the ramp generator

Advertising