4 read codes (l_parread), Read codes (l_parread), Function library lenzedrive.lib – Lenze DDS Function library Drive User Manual

Page 65: Communication

Advertising
background image

Function library LenzeDrive.lib

Communication

2.6.4

Read codes (L_ParRead)

2−55

L

LenzeDrive.lib EN 1.7

2.6.4

Read codes (L_ParRead)

This FB is used to read parameters, with Lenze so−called codes. The FB can read both the PLC codes
and codes of other devices via the system bus (CAN).

L_ParRead

bExecute

wIndex

bySubIndex

byFraction

byComChannel

wTargetAddress

wFailNumber

abyData

bFail

bBusy

bDone

VariableName

DataType

VariableType

Note

wTimeOut

Word

VAR CONSTANT

RETAIN

1 ... 65335

Time−out time in ms is the time for processing the order.

·

Initialized with 1000 ms.

·

This variable can be parameterized by means of a user
code.

bExecute

Bool

VAR_INPUT

FALSE/TRUE transition activates a read request.

wIndex

Word

VAR_INPUT

0 ... 65535

Code index
Conversion formula: Index = 24575 − code number

bySubIndex

Byte

VAR_INPUT

0 ... 255

Subindex (subcode number) of the code

byFraction

Byte

VAR_INPUT

0 ... 254

Number of decimal places of the code to be read

255

Code without decimal places
(e.g. hexadecimal code).

byComChannel

Byte

VAR_INPUT

0

Constant:

Reading a PLC code.
C_PLC

10

Constant:

Reading a code from a device connected via the system bus
(CAN).
C_SYSTEMBUS_CAN

wTargetAddress

Word

VAR_INPUT

Selecting the parameter data channel of the target device
(only with byComChannel = 10)

1 ... 64

Data transfer via SDO1 of the target device:
wTargetAddress = CAN device address of the target device

65 ... 127

Data transfer via SDO2 of the target device:
wTargetAddress = CAN device address of the target device +
64

bDone

Bool

VAR_OUTPUT

TRUE

Order has been processed (observe bFail).

bBusy

Bool

VAR_OUTPUT

TRUE

Order is being processed.

bFail

Bool

VAR_OUTPUT

TRUE

Error occurred.

wFailNumber

Word

VAR_OUTPUT

0

OK − read request was executed without error.

1

Error during data transfer via system bus (CAN).

2

External device did not respond within the set time−out time.

4

Subindex does not exist.

5

Index does not exist.

13

Parameter value to be read is not within the valid range.

117

Invalid communication channel (byComChannel).

118

There are not enough free CAN objects available.

119

The Send Order memory is full.

abyData

Byte [0 ... 3]

VAR_OUTPUT

The four data bytes with the read code value.