Function library lenzedrive.lib, Special functions, 1 control characteristic – Lenze DDS Function library Drive User Manual

Page 90

Advertising
background image

2.7.5

Process controller (L_PCTRL)

Function library LenzeDrive.lib

Special functions

2−80

L

LenzeDrive.lib EN 1.7

Parameter codes of the instances

VariableName

L_PCTRL1

SettingRange

Lenze

nVp

C0222

0.1 ... 500.0

1.0

dnTn

C0223

20 ... 99999 ms

400

nKd

C0224

0.0 ... 5.0

0.0

nVp2Adapt

C0325

0.1 ... 500.0

1.0

nVp3Adapt

C0326

0.1 ... 500.0

1.0

nSet1Adapt

C0328

0.00 ... 100.00 %

0.00

nSet2Adapt

C0327

0.00 ... 100.00 %

100.00

byPCharacteristic

C0329

0 ... 3

0

dnTir

C0332

0.000 ... 999.900 sec

0.000

dnTif

C0333

0.000 ... 999.900 sec

0.000

bBiUnipolar

C0337

0 ... 1

0

Range of functions

·

Control characteristic

·

Ramp generator

·

Value range of the output signal

·

Evaluation of the output signal

·

Deactivation of the process controller

2.7.5.1

Control characteristic

In the default setting, the PID algorithm is active.

Differential component K

d

You can deactivate the K

d

−component by setting nKd = 0.0. The controller now becomes a

PI−controller (or P−controller if the I−component is also switched off).

Integral−action component I

You can switch off the I−component with

·

bIOff_b = TRUE, or on with

·

bIOff_b = FALSE.

Switching on and off can also be done online. If the I−component is to be switched off permanently,
set bIOff_b to TRUE.

Integral−action time T

n

By using nTn you can set the parameter for the integral−action time.