Function library LenzeDrive.lib

Signal conversion

2.5.1

Normalization (L_CONV)

2−49

L

LenzeDrive.lib EN 1.7

2.5

Signal conversion

2.5.1

Normalization (L_CONV)

This FB normalizes signals. The calculation is made quite precisely, with remainder processing and
definition of the conversion factor as a numerator and denominator.

n I n _ a

n O u t _ a

L _ C O N V

n N u m e r a t o r
n D e n o m i n a t o r

Fig. 2−59

Normalization (L_CONV)

VariableName

DataType

SignalType

VariableType

Note

nIn_a

Integer

analog

VAR_INPUT

100 %

º16384 º C0011 (n

max

)

nOut_a

Integer

analog

VAR_OUTPUT

The signal it limited to ±199.99 % (100 %

º 16384).

nNumerator

Integer

VAR CONSTANT RETAIN

Numerator

nDenominator

Integer

VAR CONSTANT RETAIN

Denominator

Parameter codes of the instances

VariableName

L_CONV1

L_CONV2

L_CONV3

SettingRange

Lenze

nNumerator

C0940

C0945

C0950

−32767 ... 32767

1

nDenominator

C0941

C0946

C0951

1 ... 32767

1

VariableName

L_CONV4

L_CONV5

L_CONV6

SettingRange

Lenze

nNumerator

C0955

C0655

C1170

−32767 ... 32767

1

nDenominator

C0956

C0656

C1171

1 ... 32767

1

Function

The multiplication or division of signals is made according to the formula:

nOut

+ nIn @ nNumerator

nDenominator