3 communication function parameters, 1 fb90 (fb drive), Communication function parameters – Lenze Drive Server Bus server S7 getting started User Manual

Page 39: Fb90 (fb drive), Busserver s7

Advertising
background image

Busserver S7

L

100

Busserver S7 DE/EN 1.0

6.3

Communication function parameters

6.3.1

FB90 (FB DRIVE)

Function block

For every drive one instance is to be created.

The function block is based on the functions SFC14/15.

Parameters

Data type

Possible values/meaning

Tag

IN: STRING

Special identifier; do not change

PB_Address

IN: BYTE

0...31 PROFIBUS address of the drive (hexadecimal)

Address 1 = 1, address 15 = F

EA_Address

IN: INT

I/O address of the drive (decimal)

DriveServer_DB IN: BLOCK_DB

Data block with parameter data job list via OPC

e.g.

DB80

DrivePar_DB

IN: BLOCK_DB

Data block with parameter data job list of the PLC

e.g.

DB81

TimerNo

IN: TIMER

Timer for monitoring the drive

e.g.

T1

TimeOut

IN: S5TIME

Timeout for monitoring.

If not indicated, pre-setting ”S5T#1S” (= 1 s) is used.

Busy

OUT: BYTE

Status of the function:

usy

OU

0x00 Not active (jobs have been processed)
0x01 Active (jobs are still being processed)
0x10 Incorrect identifier in the data block, incorrect data block

indicated or overwritten: Reload data block

0x11 PB_Address incorrect (permissible values: 1 ... 123)
0x40 Count outside the range 0 ... 31
0xF0 No module configured under PB_Address
0xF1 Length of source range <> Length of configured user

data

0xFF General I/O access error