L

116

Busserver S7 DE/EN 1.0

6.6

Example project S7-300 with PROFIBUS-CP

The example project ”LenzeDriveServer” described in this chapter can be found in the sub-directory

\S7 of the DriveServer installation.

6.6.1

Hardware configuration

•

An S7-300 station is used as PLC.

•

CPU 315-2 DP, CP 342-5 and power supply PS 307 10A are configured in a RACK 300.

•

A PROFIBUS-DP sub-network with master system No. 1 (connected to the CPU) and another

sub-network with master system No. 180 (connected to the CP) are available. The drive

controllers are connected to the second master system.

•

Lenze fieldbus modules of type 2133 and 2131 are used as DP slave. These fieldbus modules

can be used for 8200 and 9300 drive controllers.

–

PROFIBUS addresses: 4 and 5 (hexadecimal)

–

Consistent communication with 8-byte parameter data and 4 process data words

(Configuration ”PAR(Kons.)+PZD(4Worte)”)

The following figure shows the hardware configuration in the Hardware Manager: