Busserver S7

L

112

Busserver S7 DE/EN 1.0

6.5.4

OB1/ FC4

With

OB1, only the function FC4 is called, in which all other blocks are called.

6.5.5

Process data transfer

FC4, network 1

The following call is used to transmit two process data words (2PZD).

Process data word 1 is always the DRIVECOM control word.

Process data word 2 can be freely selected.

CALL FC 92

//FC92, 2 PZD

EA_Address

:=1008

//I-address, decimal

Enable

:=”Enable”

//BOOL

QSP

:=”QSP”

//BOOL

Reset

:=”Reset”

//BOOL

Setpoint1

:=”Setpoint1”

//INT, decimal

ControlWord

:=”ControlWord”

//WORD, control word

RDY

:=”RDY”

//OUT, BOOL

TRIP

:=”TRIP”

//OUT, BOOL

ActualValue1

:=”ActualValue1” //OUT, INT

StatusWord

:=”StatusWord”

//OUT, status word

The start address for the process data channel can be obtained from the hardware

configuration. (here: 1008)

The inputs Enable, QSP and Reset are set to enable the controller:

Enable = TRUE

QSP = FALSE

Reset = FALSE

The second process data word is assigned to the setpoint input.

Control word and status word conform to the DRIVECOM specification.

The DRIVECOM status machine has already been implemented in

FC92.

The outputs RDY and TRIP provide information about the controller status.

ActualValue1 is the value read out.

Tip!

Detailed information about the parameters of

FC92 can be found in chapter 6.3.5.

(

^ 105)

Use function block

FC91 to transmit three process data words.

(