Busserver S7

L

103

Busserver S7 DE/EN 1.0

Possible values/meaning

Data type

Parameters
R_Value

OUT: DINT

Read value (FIX32)

R_Value

OUT: DINT

If Status= 0x83, an I/O error occurred:

F0 F0 F0 F0 Module does not exist or SFC is not available

(decimal: -252 645 136)

F1 F1 F1 F1 Data length <> 8 bytes

(decimal: -235 802 127)

FF FF FF FF Other I/O error

(decimal: -1)

If Status = 0x80, the drive controller indicated an error.

Additional error codes and further explanations can be found in the

descriptions for the individual PROFIBUS interface modules.

06 03 00 00 No access permission
06 05 00 10 Unpermissible job parameter
06 05 00 11 Invalid sub-index
06 05 00 12 Data length too long
06 07 00 00 Object does not exist
06 08 00 00 Data types do not correspond
08 00 00 20 Job cannot be executed at present
08 00 00 21 Cannot be executed because of local control
08 00 00 22 Cannot be executed because of operating state of device
08 00 00 30 Value range has been exceeded
08 00 00 40 Collision with other values

Trigger

INOUT: BOOL

TRUE Start job processing.

Automatically reset to FALSE, when the job has been

completely processed and the result is available.