Process data transfer

FC3, network 1

The following call is used to transmit two process data words (2PZD).

Process data word 1 is always the DRIVECOM control word.

Process data word 2 can be freely selected.

CALL FC 94
FirstDriveDW

:=8

DriveSend_DB

:=”DriveSend_DB”

DriveRecv_DB

:=”DriveRecv_DB”

Enable

:=”Enable”

QSP

:=”QSP”

Reset

:=”Reset”

Setpoint1

:=”Setpoint1”

ControlWord

:=”ControlWord”

RDY

:=”RDY”

TRIP

:=”TRIP”

ActualValue1

:=”ActualValue1”

StatusWord

:=”StatusWord”

The parameter FirstDriveDW defines the byte position of the first data word of the connected

drive controller.

For each drive controller, 8 data words are reserved in the data blocks

DriveSend_DB and /

or

DriveRecv_DB. The first 4 data words are needed for parameter access and the last 4

data words for process data access.

The drive controllers must have successive I/O addresses.

The inputs Enable, QSP and Reset are set to enable the controller:

Enable = TRUE

QSP = FALSE

Reset = FALSE

The second process data word is assigned to the setpoint input.

Control word and status word conform to the DRIVECOM specification.

The DRIVECOM status machine has already been implemented in

FC94.

The outputs RDY and TRIP provide information about the controller status.

ActualValue1 is the value read out.

Tip!

Detailed information about the parameters of

FC94 can be found in chapter 6.3.7.

(

^ 107)

Use function block

FC93 to transmit three process data words.

(