Example project S7-400

The example project ”LenzeDriveServer” described in this chapter can be found in the sub-directory

\S7 of the DriveServer installation.

6.5.1

Hardware configuration

An S7-400 station is used as PLC.

CPU 412-2 DP and power supply PS 407 10A are configured in a RACK 400.

A PROFIBUS-DP sub-network with master system No. 1 and a baud rate of 1.5 Mbit/s is

available.

A Lenze fieldbus module of type 2131 is used as DP slave. This fieldbus module can be used for

8200 and 9300 drive controllers.

PROFIBUS address: 9 (hexadecimal)

Start address of parameter channel: 1000

Start address of process data channel: 1008

Consistent communication with 8-byte parameter data and 2 process data words

(Configuration ”PAR(8ByteKons.)+PZD(2Worte)”)

The following figure shows the hardware configuration in the Hardware Manager:

Tip!

The slot table in the Hardware Manager lists the settings of the parameter channel (slot 0) and the

process data channel (slot 1).
The data provided in the columns

I-address and O-address are required to call the function FC92 in

the PLC program: