3 technical data, Technical data, Safety option 10 – Lenze SO30 8400 protec User Manual

Page 17

Advertising
background image

Safety option 10

Technical data

3

l

17

EDS84DPSO01 EN 2.1

3.3

Technical data

Supply

The safe input and the output are isolated and designed for a low−voltage supply through
a safely separated power supply unit (SELV/PELV) of 24 V DC. P/N switching input signals
and test pulses

£ 1 ms are permissible.

Active sensors are directly connected to the X61 circular connector.

Passive sensors are connected to the X61 circular connector via a switching device. The
switching device must comply with the required performance level of the application.

There is no monitoring for short circuits.

Detailed features of the inputs and outputs of the safety unit

Terminal

Specification

[Unit]

min.

typ.

max.

SIA, SIB

Low signal

V

−3

0

5

High signal

V

18

24

30

Input capacitance at switch−off

nF

3

Input delay (tolerated test pulse)

ms

1

Switch−off time (depending on the controller)

ms

2.5

4

Running time

ms

3

Input current

mA

45

50

Input capacitance at switch−on, reduced

mF

22

GI

GND potential for SIA / SIB and for the non−safe
signalling output

24O

Supply voltage through safely separated power supply
unit (SELV/PELV)

V

18

24

30

DO

Low signal

V

0

0.8

High signal

V

18

24

30

24O, DO

Output current

A

0.2

Truth table

Safe input / channel

Signalling

output

Controller

SIA

SIB

DO1/DO

Description of device status

Enable

0

0

1

"Safe torque off" activated

0

0

1

0

0

1

0

0

0

1

1

0

Drive active

1

)

Note!

Safe inputs have two channels (...A/...B). The channels must be triggered
separately and simultaneously (equivalent).
Active triggering of only one channel indicates faulty sensors or impermissible
wiring.
Despite this, the integrated safety system is activated as soon as at least one
channel has been triggered.