Safety option 20

Operating mode

Disconnecting paths

4

l

21

EDS84DPSO01 EN 2.1

4.1.2

Disconnecting paths

The transmission of the pulse width modulation is safely switched (off) by the safety unit.
After this, the power drivers do not generate a rotating field. The motor is safely switched
to torqueless operation (STO).

M

SO

PWM

µC

P

C

3x

3x

Xxx

E84DPSO02

Fig. 4−1

Operating principle of safety unit

SO

Safety option 10, 20, or 30

xxx

Control terminals used in safety engineering systems or safety bus

C

Control section

mC

Microcontroller

PWM

Pulse width modulation

P

Power section

M

Motor

4.1.3

Safety status

When the controller is disconnected from the safety unit, the "Safe torque off" (STO) status
is set (C00155 bit 10 = 1).

4.1.4

Fail−safe status

When internal errors of the safety unit are detected, the motor is safely switched to
torqueless operation (fail−safe status).