Safety option 30

Response times

5

l

61

EDS84DPSO01 EN 2.1

5.9

Response times

In order to detect the response time to a safety function the entire system must be
considered. The following is relevant:

ƒ

Response time of the connected sensors.

ƒ

Input delay of the safety inputs.

ƒ

Internal processing time.

ƒ

When using PROFIsafe as safety bus:
– Monitoring time for the cyclic service in the PROFIBUS/PROFINET.
– Monitoring time of the PROFIsafe in the safety PLC.
– Processing time in the safety PLC.

ƒ

Delay times due to further components.

μC

μC

S

SF

t = 0

t

1

t

2

0

1

t

ps

t

4

2

3

t

3

t

5

t

i

lcu12x_352

Fig. 5−6

Response times to the request of a safety function
0 Standard device

1 Drive−based safety

2 Safety PLC

3 Safety bus

mC Microcontroller
S

Safety sensor technology

SF

Activated safety function