Safety option 30

Operating mode

Safe inputs

5

l

37

EDS84DPSO01 EN 2.1

5.1.5

Safe inputs

Contact function test

)

Note!

Make sure that an internal contact function test is carried out at the safe
inputs:
Safe input in the ON state

ƒ

A LOW level at one channel puts the input in the OFF state. The discrepancy
monitoring starts simultaneously.

ƒ

A LOW level must be detected at both channels within the discrepancy time,
otherwise a discrepancy error will be reported.

ƒ

To be able to acknowledge the discrepancy error, a LOW level must be
detected before at both channels.

Safe input in the OFF state

ƒ

A HIGH level at one channel starts the discrepancy monitoring.

ƒ

A HIGH level must be detected at both channels within the discrepancy
time, otherwise a discrepancy error will be reported.

ƒ

To be able to acknowledge the discrepancy error, a HIGH level must be
detected before at both channels.

Switch both channels

to ON state

Switch both channels

to OFF state

One channel in

ON state

One channel in

OFF state

Value of safe input:

OFF state

Value of safe input:

OFF state

Value of safe input:

OFF state

Value of safe input:

ON state

Discrepancy monitoring

Discrepancy monitoring

OFF state

ON state

SSP94SM355

Fig. 5−2

Status behaviour − contact function test