Module error messages

Entries

Range

Description

Error type/response/
Note

Error number

Communication − standard device

16

0x10

Communication error − standard device
(communication between standard device and SM301 cancelled)

Warning/STO

17

0x11

Synchronisation error − standard device

No error status
Logbook entry/info

PROFIsafe

34

0x22

PROFIsafe communication error

PROFIsafe passivated/−
No error status
No diagnostic telegram via
PROFINET

35

0x23

F_WD_Time exceeded
(PROFIsafe monitoring time activated)

36

0x24

PROFIsafe deactivated

37

0x25

PROFIsafe has quit Data Exchange

38

0x26

PROFIsafe invalid data

39

0x27

Error − F parameter
(Wrong parameter setting of the F PLC)

PROFIsafe parameter
setting/STO
No error status

Inputs

49

0x31

Error − discrepancy or functional test SD−In1

Trouble/−
OFF state for the affected
input

50

0x32

Error − discrepancy or functional test SD−In2

53

0x35

Internal error AIS

54

0x36

Internal error AIE

55

0x37

Internal error − module switch

57

0x39

Deactivated SD−In1 = high
(Initialisation error, input in ON state)

Trouble/STO

58

0x3A

Deactivated SD−In2 = high

PROFIsafe

64

0x40

F_Dest_Add does not equal F address

PROFIsafe parameter
setting/STO
No error status

65

0x41

F_Dest_Add = 0 or FFFFhex

66

0x42

F_Source_Add = 0 or FFFFhex

67

0x43

F_WD_Time is 0 msec

68

0x44

F_SIL exceeds technical SIL

69

0x45

F_CRC_Length error

70

0x46

F parameter version incorrect

71

0x47

PROFIsafe CRC1 error

72

0x48

reserved (PS standard)

73

0x49

reserved (PS standard)

74

0x4A

reserved (PS standard)

Test functions

81

0x51

Error SD−Inx/CLx
(internal short circuit in one of the inputs)

Trouble/−
OFF state for all SD−In

93 0x5D

Error − internal disconnecting path
(internal error of the safe switch−off logic)

Trouble/STO
OFF state for all SD−In

94

0x5E

Test pulse error − internal switch−off path
(internal error of the safe switch−off logic)

Trouble/STO

Safety functions

97

0x61

SS1: Stopping time exceeded
(The drive has not reached zero speed within the stopping time.)

Warning/STO