Cabling requirements – Rockwell Automation 22-SCM-232 Serial Converter Module User Manual

Page 30

Advertising
background image

4-2

Controlling PowerFlex 4 and 40 Drives with Allen-Bradley Controllers

Figure 4.1 Point-to-Point Example

Figure 4.2 Multiple Drive Example

In addition to using the 22-SCM-232 serial converter module, the
required cabling depends on the type of Allen-Bradley controller being
used:

AB

Drive

22-SCM-232

Serial Converter

Controller

RS232

DF1

RS485

Modbus RTU

AB

Drive # 1

22-SCM-232

Serial Converter

Controller

RS232

DF1

RS485

Modbus RTU

Drive # 2

Drive # 31

AK-U0-RJ45-SC1

Splitter Cable

AK-U0-RJ45-TB2P

Terminal Blocks

1/4W, 120

Ω

Terminating Resistors

(on first and last drives)

Cabling Requirements

Controller Type

Requires 22-SCM-232 plus

MicroLogix 1000/1200/1500
LSP

1761-CBL-PM02 or 1761-CBL-AP00 (8-pin DIN to 9-pin
Female) and 1203-SNM Serial Null Modem adapter (9-pin
Male to 9-pin Male)

MicroLogix 1500 LRP

SLC 5/03, 5/04 or 5/05

PLC5

9-pin Male to 25-pin Male adapter (3rd party)

ControlLogix/CompactLogix —

Advertising