Ilogic command/status words, Appendix, Powerflex 4 and powerflex 40 drives – Rockwell Automation 22-SCM-232 Serial Converter Module User Manual

Page 93

Advertising
background image

Appendix

I

Logic Command/Status Words

Appendix I provides the definitions of the Logic Command/Logic Status
words that are used for some products that can be connected to the
22-SCM-232 serial converter module. If you do not see the Logic
Command/Logic Status for the product that you are using, refer to your
product’s documentation.

Logic Command Word

* A 0 = Not Stop condition (logic 0) must first be present before a 1 = Start condition will start the drive.

PowerFlex 4 and PowerFlex 40 Drives

Logic Bits
15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0 Command Description

x Stop

0 = Not Stop
1 = Stop

x

Start*

0 = Not Start
1 = Start

x

Jog

0 = Not Jog
1 = Jog

x

Clear
Faults

0 = Not Clear Faults
1 = Clear Faults

x x

Direction

00 = No Command
01 = Forward Command
10 = Reverse Command
11 = Change Direction (toggle)

x

Not used

x

MOP
Increment

0 = Not Increment
1 = Increment

x x

Accel Rate 00 = No Command

01 = Accel Rate 1 Command
10 = Accel Rate 2 Command
11 = Hold Accel Rate

x

x

Decel Rate 00 = No Command

01 = Decel Rate 1 Command
10 = Decel Rate 2 Command
11 = Hold Decel Rate

x

x

x

Reference
Select

000 = No Command
001 = Freq Source = Select
010 = Freq Source = Int. Freq
011 = Freq Source = Comm
100 = Preset Freq 1
101 = Preset Freq 2
110 = Preset Freq 3
111 = Preset Freq 4

x

MOP
Decrement

0 = Not Decrement
1 = Decrement