Events – Rockwell Automation 22-SCM-232 Serial Converter Module User Manual

Page 36

Advertising
background image

5-4

Troubleshooting

Events

Many events in the Event queue occur under normal operation. If you
encounter unexpected communications problems, the events may help
you or Allen-Bradley personnel troubleshoot the problem. The following
events may appear in the event queue:

To clear the event queue

1. Access the event queue using a configuration tool. Refer to the

Configuration Tools

section in

Chapter 3

.

2. Set the value of 1 > Clr Event Queue to Enable, and then press

Enter to clear the event queue.

Figure 5.3 Reset Event Queue in HyperTerminal

Code

Event

Description

F0

No Event

No event present in the module event queue.

F1

Adapter Reset

The module was reset by the user.

F2

Slave Detected

Slave was detected to be present by master.

F3

Slave Removed

Slave was detected to be removed by master.

F4

Host Timeout

Timeout condition on Msg to Host.

F5

Slave Timeout

Timeout condition on Msg to Slave.

F6

Master Timeout

Timeout condition on Msg to Master.

F7

Serial Timeout

Timeout on Serial 232 side (w/control enabled).

F8

Control Enabled

The module has sent a “Soft Control Enable” command
to the drive.

F9

Control Disabled

The module has sent a “Soft Control Disable”
command to the drive.

F10

EEPROM Sum Flt

Startup sequence detected corrupt EEPROM storage
in the module.

Press the UP ARROW or DOWN ARROW key to scroll

through the parameter list. Press the LEFT ARROW or

RIGHT ARROW key to modify parameter values. Press

the ENTER key to save a new value.

1> Clr Event Queue = Enable