MicroLogix 1200/1500 Example Ladder Program

E-3

Figure E.1 Example MicroLogix 1200/1500 Ladder Logic Program (Continued)

0005

I:0

4

Bul.1764

Fwd / Rev
SS

N7:20

4

Logic Command
FORWARD

0006

I:0

4

Bul.1764

Fwd / Rev
SS

N7:20

5

Logic Command
REVERSE

For demonstration purposes, the value of analog POT0 on the LRP processor is used to generate the
Reference. Since the pot has a range of 0-250 (equates to 0.0 to 25.0 Hz), the pot value is multiplied by 3
to provide a range of 0 to 750 (0.0 to 75.0 Hz). Note that P034 [Minimum Freq] and P035 [Maximum
Freq] on the drive determine the actual output frequency range on the drive. The default is 0.0 to 60.0 Hz.

0007

MUL

Multiply
Source A TPI:0.POT0
0<
Source B

3

3<
Dest

N7:21

336<

MUL

Reference

Write the Logic Command (N182:192) and Reference (N182:193) to the drive.

0008

EN

DN

ER

MSG

Read/Write Message
MSG File

MG11:0

Setup Screen

MSG

Starts the message cycle over again

0009

MG11:0

DN

MG11:0

ER

U

MG11:0

EN

Reads a block of data (starting at N183:198) containing:

N7:10 Logic Status (N183:198)
N7:11 Drive Error Codes (N183:199)
N7:12 Frequency Command (= Reference) (N183:200)
N7:13 Output Frequency (Feedback) (N183:201)
N7:14 Output Current (N183:202)
N7:15 DC Bus Voltage (N183:203)
N7:16 Output Voltage (N183:204)

0010

EN

DN

ER

MSG

Read/Write Message
MSG File

MG11:2

Setup Screen

MSG