MicroLogix 1000 Example Ladder Program

D-3

Figure D.1 Example MicroLogix 1000 Ladder Logic Program (Continued)

This rung sets the timeout value for the second MSG instruction.

0002

N7:60

15

Enable
(EN)

N7:60

12

Error
(ER)

N7:60

13

Done
(DN)

EN

DN

TON

Timer On Delay
Timer

T4:1

Time Base

0.01

Preset

200<

Accum

0<

TON

MSG #2
Time Out
Timer

T4:1

DN

MSG #2
Time Out
Timer

L

N7:60

8

Time Out
(TO)

This rung sets the timeout value for the third MSG instruction.

0003

N7:70

15

Enable
(EN)

N7:70

12

Error
(ER)

N7:70

13

Done
(DN)

EN

DN

TON

Timer On Delay
Timer

T4:2

Time Base

0.01

Preset

200<

Accum

0<

TON

MSG #3
Time Out
Timer

T4:2

DN

MSG #3
Time Out
Timer

L

N7:70

8

Time Out
(TO)

This rung sets the timeout value for the fourth MSG instruction.

0004

N7:80

15

Enable
(EN)

N7:80

12

Error
(ER)

N7:80

13

Done
(DN)

EN

DN

TON

Timer On Delay
Timer

T4:3

Time Base

0.01

Preset

200<

Accum

0<

TON

MSG #4
Time Out
Timer

T4:3

DN

MSG #4
Time Out
Timer

L

N7:80

8

Time Out
(TO)