Reflected wave protection, Output disconnect – Rockwell Automation 22A PowerFlex 4 User Manual FRN 6.xx User Manual

Page 19

Advertising
background image

Installation/Wiring

1-9

Reflected Wave Protection

The drive should be installed as close to the motor as possible.
Installations with long motor cables may require the addition of external
devices to limit voltage reflections at the motor (reflected wave
phenomena). See

Table 1.E

for recommendations.

The reflected wave data applies to all frequencies 2 to 16 kHz.

For 240V ratings, reflected wave effects do not need to be considered.

Table 1.E Maximum Cable Length Recommendations

Output Disconnect

The drive is intended to be commanded by control input signals that will
start and stop the motor. A device that routinely disconnects then
reapplies output power to the motor for the purpose of starting and
stopping the motor should not be used. If it is necessary to disconnect
power to the motor with the drive outputting power, an auxiliary contact
should be used to simultaneously disable drive control run commands.

Reflected Wave

380-480V Ratings

Motor Insulation Rating

Motor Cable Only

(1)

(1)

Longer cable lengths can be achieved by installing devices on the output of the drive.
Consult factory for recommendations.

1000 Vp-p

15 meters (49 feet)

1200 Vp-p

40 meters (131 feet)

1600 Vp-p

170 meters (558 feet)

Advertising