A080, A081, A079 – Rockwell Automation 22A PowerFlex 4 User Manual FRN 6.xx User Manual

Page 53: Advanced program group, Continued), A079 [jog accel/decel, A080 [dc brake time, A081 [dc brake level, Programming and parameters 3-17

Advertising
background image

Programming and Parameters

3-17

Advanced Program Group

(continued)

A079 [Jog Accel/Decel]

Related Parameter(s):

A051

,

A052

,

A078

Sets the acceleration and deceleration time when a jog command is issued.

Values

Default

10.0 Secs

Min/Max:

0.1/600.0 Secs

Display:

0.1 Secs

A080 [DC Brake Time]

Related Parameter(s):

P037

,

A081

Sets the length of time that DC brake current is “injected” into the motor. Refer to parameter

A081

[DC

Brake Level].

Values

Default

0.0 Secs

Min/Max:

0.0/90.0 Secs

Display:

0.1 Secs

A081 [DC Brake Level]

Related Parameter(s):

P037

,

A080

Defines the maximum DC brake current, in amps, applied to the motor when

P037

[Stop Mode] is set

to either “Ramp” or “DC Brake”.

Values

Default

Drive Rated Amps

×

0.05

Min/Max:

0.0/(Drive Rated Amps

×

1.8)

Display:

0.1 Amps

DC Injection Braking Mode

V

olts/S

p

eed

Voltage

Time

Stop Command

Speed

[DC Brake Level]

[DC Brake Time]

V

olts/S

p

eed

Ramp-to-Stop Mode

Time

Stop Command

[DC Brake Level]

[DC Brake Time]

Voltage

Speed

!

ATTENTION:

If a hazard of injury due to movement of equipment or material exists,

an auxiliary mechanical braking device must be used.

!

ATTENTION:

This feature should not be used with synchronous or permanent

magnet motors. Motors may be demagnetized during braking.