A084, A088, Advanced program group – Rockwell Automation 22A PowerFlex 4 User Manual FRN 6.xx User Manual
Page 55: Continued), A084 [boost select, A088 [maximum voltage, Programming and parameters 3-19

Programming and Parameters
3-19
Advanced Program Group
(continued)
A084 [Boost Select]
Related Parameter(s):
,
Sets the boost voltage (% of
[Motor NP Volts]) and redefines the Volts per Hz curve.
(1)
(1)
Drive may add additional voltage unless option 5 is selected.
Options
1 “30.0, VT”
Variable Torque
2 “35.0, VT”
3 “40.0, VT”
4 “45.0, VT”
5 “0.0 no IR”
Constant Torque
6 “0.0”
7 “2.5, CT”
[Default for 3.7kW
(5HP) Drives]
8 “5.0, CT” (Default)
9 “7.5, CT”
10 “10.0, CT”
11 “12.5, CT”
12 “15.0, CT”
13 “17.5, CT”
14 “20.0, CT”
% P032 [Motor NP Hertz]
% P031 [Motor NP Volts]
100
50
1/2 [Motor NP Volts]
1/2
[Motor NP Hertz]
4
3
2
1
0
50
100
Settings
5-14
A088 [Maximum Voltage]
Sets the highest voltage the drive will output.
Values
Default
Drive Rated Volts
Min/Max:
20/Drive Rated Volts
Display:
1 VAC