16 installation/wiring – Rockwell Automation 22A PowerFlex 4 User Manual FRN 6.xx User Manual

Page 26

Advertising
background image

1-16

Installation/Wiring

3 Wire SRC Control -
Non-Reversing

P036

[Start Source] = 1

A momentary input will
start the drive. A stop
input to I/O Terminal 01
will stop the drive as
specified by

P037

[Stop

Mode].

Internal Supply (SRC)

External Supply (SRC)

3 Wire SNK Control -
Non-Reversing

Internal Supply (SNK)

3 Wire SRC Control -
Reversing

P036

[Start Source] = 1

A momentary input will
start the drive. A stop
input to I/O Terminal 01
will stop the drive as
specified by

P037

[Stop

Mode]. I/O Terminal 03
determines direction.

Internal Supply (SRC)

External Supply (SRC)

3 Wire SNK Control -
Reversing

Internal Supply (SNK)

Input

Connection Example

11

01

02

Stop

Start

01

02

04

+24V

Common

Stop

Start

Each digital input draws 6 mA.

Stop

Start

01

02

03

04

11

01

02

03

Stop

Start

Direction

+24V

Common

Stop

Start

Direction

01

02

03

04

Each digital input draws 6 mA.

Stop

Start

Direction

01

02

03

04