Reading (03) drive error codes, Reading (03) and writing (06) drive parameters, Additional information – Rockwell Automation 22A PowerFlex 4 User Manual FRN 6.xx User Manual
Page 97: Rs485 (dsi) protocol c-5, Refer to, For additional information

RS485 (DSI) Protocol
C-5
Reading (03) Drive Error Codes
The PowerFlex 4 Error Code data can be read via the network by sending
Function Code 03 reads to register address 8449 (Drive Error Codes).
Reading (03) and Writing (06) Drive Parameters
To access drive parameters, the Modbus register address equals the
parameter number. For example, a decimal “1” is used to address
Parameter d001 [Output Freq] and decimal “39” is used to address
Parameter P039 [Accel Time 1].
Additional Information
Refer to
http://www.ab.com/drives/
for additional information.
Logic Status
Address (Decimal)
Value (Decimal)
Description
8449
0
No Fault
2
Auxiliary Input
3
Power Loss
4
Undervoltage
5
Overvoltage
6
Motor Stalled
7
Motor Overload
8
Heatsink Overtemperature
12
HW Overcurrent (300%)
13
Ground Fault
29
Analog Input Loss
33
Auto Restart Tries
38
Phase U to Ground Short
39
Phase V to Ground Short
40
Phase W to Ground Short
41
Phase UV Short
42
Phase UW Short
43
Phase VW Short
63
Software Overcurrent
64
Drive Overload
70
Power Unit Fail
80
AutoTune Fail
81
Communication Loss
100
Parameter Checksum Error
122
I/O Board Fail