P037 [Stop Mode]

Related Parameter(s):

P036

,

A080

,

A081

,

A082

,

A105

Active stop mode for all stop sources [e.g. keypad, run forward (I/O Terminal 02), run reverse (I/O
Terminal 03), RS485 port] except as noted below.
Important: I/O Terminal 01 is always a coast to stop input except when

P036

[Start Source] is set for

“3-Wire” control. When in three wire control, I/O Terminal 01 is controlled by

P037

[Stop Mode].

Hardware Enable Circuitry
By default, I/O Terminal 01 is a coast to stop input. The status of the input is interpreted by drive
software. If the application requires the drive to be disabled without software interpretation, a “dedicat-
ed” hardware enable configuration can be utilized. This is accomplished by removing the ENBL
enable jumper on the control board. In this case, the drive will always coast to a stop regardless of the
settings of

P036

[Start Source] and

P037

[Stop Mode].

Options

0 “Ramp, CF”

(1)

(Default) Ramp to Stop. “Stop” command clears active fault.

1 “Coast, CF”

(1)

Coast to Stop. “Stop” command clears active fault.

2 “DC Brake, CF

(1)

DC Injection Braking Stop. “Stop” command clears active
fault.

3 “DCBrkAuto,CF

(1)

DC Injection Braking Stop with Auto Shutoff.

Standard DC Injection Braking for value set in

A080

[DC

Brake Time].
OR

Drive shuts off if the drive detects that the motor is
stopped.

“Stop” command clears active fault.

4 “Ramp”

Ramp to Stop.

5 “Coast”

Coast to Stop.

6 “DC Brake”

DC Injection Braking Stop.

7 “DC BrakeAuto”

DC Injection Braking Stop with Auto Shutoff.

Standard DC Injection Braking for value set in

A080

[DC

Brake Time].
OR

Drive shuts off if current limit is exceeded.

(1)

Stop input also clears active fault.