A103, A102, Advanced program group – Rockwell Automation 22A PowerFlex 4 User Manual FRN 6.xx User Manual
Page 59: Continued), A100 [fault clear, A101 [program lock, A102 [testpoint sel, A103 [comm data rate, A104 [comm node addr

Programming and Parameters
3-23
Advanced Program Group
(continued)
A100 [Fault Clear]
Stop drive before changing this parameter.
Resets a fault and clears the fault queue. Used primarily to clear a fault over network communications.
Options
0 “Ready/Idle” (Default)
1 “Reset Fault”
2 “Clear Buffer”
(Parameters
[Fault x Code])
A101 [Program Lock]
Protects parameters against change by unauthorized personnel.
Options
0 “Unlocked” (Default)
1 “Locked”
A102 [Testpoint Sel]
Used by Rockwell Automation field service personnel.
Values
Default
400
Min/Max:
0/FFFF
Display:
1 Hex
A103 [Comm Data Rate]
Related Parameter(s):
Sets the serial port rate for the RS485 (DSI) port.
Important: Power to drive must be cycled before any changes will affect drive operation.
Options
0 “1200”
1 “2400”
2 “4800”
3 “9600” (Default)
4 “19.2K”
5 “38.4K”
A104 [Comm Node Addr]
Related Parameter(s):
Sets the drive node address for the RS485 (DSI) port if using a network connection.
Important: Power to drive must be cycled before any changes will affect drive operation.
Values
Default
100
Min/Max:
1/247
Display:
1