A090, A089, Advanced program group – Rockwell Automation 22A PowerFlex 4 User Manual FRN 6.xx User Manual

Page 56: Continued), A089 [current limit, A090 [motor ol select, A091 [pwm frequency, 20 programming and parameters

Advertising
background image

3-20

Programming and Parameters

Advanced Program Group

(continued)

A089 [Current Limit]

Maximum output current allowed before current limiting occurs.

Values

Default

Drive Rated Amps

×

1.5

Min/Max:

0.1/(Drive Rated Amps

×

1.8)

Display:

0.1 Amps

A090 [Motor OL Select]

Related Parameter(s):

P032

Drive provides Class 10 motor overload protection. Settings 0-2 select the derating factor for the I

2

t

overload function.

Options

0 “No Derate” (Default)

1 “Min Derate”

2 “Max Derate”

Min Derate

0

80

100

60

40

20

No Derate

0

80

100

60

40

20

%

of P033

[Motor OL Curent

]

Max Derate

0

80

100

60

40

20

0

200

175

150

125

100

75

50

25

0

200

175

150

125

100

75

50

25

0

200

175

150

125

100

75

50

25

A091 [PWM Frequency]

Sets the carrier frequency for the PWM output waveform. The chart below provides derating
guidelines based on the PWM frequency setting.
Important: Ignoring derating guidelines can cause reduced drive performance.

Values

Default

4.0 kHz

Min/Max:

2.0/16.0 kHz

Display:

0.1 kHz

68

84

88

80
76

96

100

92

72

64
60
56
52

8

7

6

5

4

3

2

1

15

14

16

13

12

11

10

9