Programming and Parameters

3-11

Basic Program Group

(continued)

P038 [Speed Reference]

Related Parameter(s):

d001

,

d002

,

d012

,

P039

,

P040

,

A051

,

A052

,

A069

,

A070

-

A073

,

A110

,

A111

,

A112

,

A113

Sets the source of the speed reference to the drive.
The drive speed command can be obtained from a number of different sources. The source is
normally determined by

P038

[Speed Reference]. However, when

A051

-

A052

[Digital Inx Sel] is set

to option 2, 4, 5, 6, 11, 12, 13, 14, 15 and the digital input is active, the speed reference commanded
by

P038

[Speed Reference] will be overridden. Refer to the flowchart on

page 1-18

for more

information on speed reference control priority.

Options

0 “Drive Pot” (Default)

Internal frequency command from the potentiometer on the
integral keypad.

1 “InternalFreq”

Internal frequency command from

A069

[Internal Freq].

2 “0-10V Input”

External frequency command from the 0-10V analog input or
remote potentiometer.

3 “4-20mA Input”

External frequency command from the 4-20mA analog input.

4 “Preset Freq”

External frequency command as defined by

A070

-

A073

[Preset Freq x] when

A051

and

A052

[Digital Inx Sel] are

programmed as “Preset Frequencies” and the digital inputs
are active.

5 “Comm Port”

External frequency command from the communications port.

P039 [Accel Time 1]

Related Parameter(s):

P038

,

P040

,

A051

,

A052

,

A067

,

A070

-

A073

Sets the rate of acceleration for all speed increases.

Values

Default

10.0 Secs

Min/Max:

0.0/600.0 Secs

Display:

0.1 Secs

Maximum Freq

Accel Time

Accel Rate

=

Speed

0

Time

P035 [Maximum Freq]

P039 or A067

[Accel Time x]

P040 or A068

[Decel Time x]

0

Acceleration

D

eceleration