3-24

Programming and Parameters

Advanced Program Group

(continued)

A105 [Comm Loss Action]

Related Parameter(s):

d015

,

P037

,

A106

Selects the drive’s response to a loss of the communication connection or excessive communication
errors.

Options

0 “Fault” (Default)

Drive will fault on an F81 Comm Loss and coast to stop.

1 “Coast to Stop”

Stops drive via coast to stop.

2 “Stop”

Stops drive via

P037

[Stop Mode] setting.

3 “Continu Last”

Drive continues operating at communication commanded
speed saved in RAM.

A106 [Comm Loss Time]

Related Parameter(s):

d015

,

A105

Sets the time that the drive will remain in communication loss before implementing the option selected
in

A105

[Comm Loss Action].

Values

Default

5.0 Secs

Min/Max:

0.1/60.0 Secs

Display:

0.1 Secs

A107 [Comm Format]

Selects the protocol (RTU only), data bits (8 data bits only), parity (None, Even, Odd), and stop bits (1
stop bit only) used by the RS485 port on the drive.
Refer to

Appendix C

for details on using the drive communication features.

Important: Power to drive must be cycled before any changes will affect drive operation.

Options

0 “RTU 8-N-1” (Default)

1 “RTU 8-E-1”

2 “RTU 8-O-1”

3 “RTU 8-N-2”

4 “RTU 8-E-2”

5 “RTU 8-O-2”