Programming and Parameters

3-21

Advanced Program Group

(continued)

A092 [Auto Rstrt Tries]

Sets the maximum number of times the drive attempts to reset a fault and restart.
Clear a Type 1 fault and restart the drive.
1. Set A092 [Auto Rstrt Tries] to a value other than “0”.
2. Set

A093

[Auto Rstrt Delay] to a value other than “0”.

Clear an OverVoltage, UnderVoltage or Heatsink OvrTmp fault without restarting the drive.
1. Set A092 [Auto Rstrt Tries] to a value other than “0”.
2. Set

A093

[Auto Rstrt Delay] to “0”.

Values

Default

0

Min/Max:

0/9

Display:

1

!

ATTENTION:

Equipment damage and/or personal injury may result if this parameter

is used in an inappropriate application. Do not use this function without considering
applicable local, national and international codes, standards, regulations or industry
guidelines.

A093 [Auto Rstrt Delay]

Related Parameter(s):

A092

Sets the time between restart attempts when

A092

[Auto Rstrt Tries] is set to a value other than zero.

Values

Default

1.0 Secs

Min/Max:

0.0/300.0 Secs

Display:

0.1 Secs

A094 [Start At PowerUp]

Stop drive before changing this parameter.

Enables/disables a feature that allows a Start or Run command to automatically cause the drive to
resume running at commanded speed after drive input power is restored. Requires a digital input
configured for Run or Start and a valid start contact.

This parameter will not function if parameter

P036

[Start Source] is set to 4 “2-W High Speed”.

Options

0 “Disabled” (Default)

1 “Enabled”

!

ATTENTION:

Equipment damage and/or personal injury may result if this parameter

is used in an inappropriate application. Do not use this function without considering
applicable local, national and international codes, standards, regulations or industry
guidelines.