A056, A067, A068 – Rockwell Automation 22A PowerFlex 4 User Manual FRN 6.xx User Manual
Page 51: Advanced program group, Continued), A056 [relay out level, A067 [accel time 2, A068 [decel time 2, Programming and parameters 3-15

Programming and Parameters
3-15
Advanced Program Group
(continued)
A056 [Relay Out Level]
Related Parameter(s):
32 bit parameter.
Sets the trip point for the digital output relay if the value of
[Relay Out Sel] is 6, 7, 8, 10 or 20.
Values
Default
0.0
Min/Max:
0.0/9999
Display:
0.1
32
A055 Setting
A056 Min/Max
6
7
8
10
20
0/240 Hz
0/180%
0/815 Volts
0/100%
0/1
A067 [Accel Time 2]
Related Parameter(s):
When active, sets the rate of acceleration for all speed increases except jog. Refer to the flowchart on
for details.
Values
Default
20.0 Secs
Min/Max:
0.0/600.0 Secs
Display:
0.1 Secs
Maximum Freq
Accel Time
Accel Rate
=
Speed
0
Time
P035 [Maximum Freq]
P039 or A067
[Accel Time x]
P040 or A068
[Decel Time x]
0
Acceleration
D
eceleration
A068 [Decel Time 2]
Related Parameter(s):
When active, sets the rate of deceleration for all speed decreases except jog. Refer to the flowchart
on
for details.
Values
Default
20.0 Secs
Min/Max:
0.1/600.0 Secs
Display:
0.1 Secs
Maximum Freq
Decel Time
Decel Rate
=
Speed
0
Time
P035 [Maximum Freq]
P039 or A067
[Accel Time x]
P040 or A068
[Decel Time x]
0
Acceleration
D
eceleration