P043, P040, Basic program group – Rockwell Automation 22A PowerFlex 4 User Manual FRN 6.xx User Manual

Page 48: Continued), P040 [decel time 1, P041 [reset to defalts, P043 [motor ol ret, 12 programming and parameters

Advertising
background image

3-12

Programming and Parameters

Basic Program Group

(continued)

P040 [Decel Time 1]

Related Parameter(s):

P038

,

P039

,

A051

,

A052

,

A068

,

A070

-

A073

Sets the rate of deceleration for all speed decreases.

Values

Default

10.0 Secs

Min/Max:

0.1/600.0 Secs

Display:

0.1 Secs

Maximum Freq

Decel Time

Decel Rate

=

Speed

0

Time

P035 [Maximum Freq]

P039 or A067

[Accel Time x]

P040 or A068

[Decel Time x]

0

Acceleration

D

eceleration

P041 [Reset To Defalts]

Stop drive before changing this parameter.

Resets all parameter values to factory defaults.

Options

0 “Idle State” (Default)

1 “Reset Defaults”

After the reset function is complete, this parameter will set
itself back to “0”.

Causes an F48

Params Defaulted

fault.

P043 [Motor OL Ret]

Related Parameter(s):

P033

Enables/disables the Motor Overload Retention function. When Enabled, the value held in the motor
overload counter is saved at power-down and restored at power-up. A change to this parameter
setting resets the counter.

Options

0 “Disabled” (Default)

1 “Enabled”