1-6

Installation/Wiring

PowerFlex SCR Bus Supply User Manual
Publication 20S-UM001G-EN-P

Minimum Capacitance

In order to commission and test the SCR Bus Supply, a minimum
capacitance is required. The design of the final installation must assure that
the minimum capacitance is connected whenever the bus supply is to be
enabled. If this minimum capacitance is not present, the bus supply internal
fault detection circuit will interpret the condition as a DC bus short and stop
pulse firing. The minimum capacitance (110 µF per SCR bus supply) may
be provided by an external capacitor bank (recommended) or a drive (as
long as the drive remains connected to the DC bus). NOTE: A capacitance
of 110 µF is typical of a 5 HP or 3.7 kW drive. To find DC bus capacitances
for specific PowerFlex drives, refer to Appendix A tables in the PowerFlex
AC Drives in Common Bus Configurations Application Guidelines

(publication DRIVES-AT002).

Maximum Loading

To avoid overloading the Bus Supply, the following requirement applies:

The DC Input current sum (Normal Duty rating at 40 °C/104 °F) of the
connected drive(s) must not exceed the Bus Supply continuous DC Bus
output current rating.

For the DC Input Current values of the drives, see tables in the respective
drive documentation.

Table 1.A

and

Table 1.B

provide guidance on the nominal operation of the

SCR Bus Supply. No overload capability is built into the tables.

Important: See

Output Ratings

in Appendix A for overload capability.

When an overload is being utilized in connected drives or products, that
overload current must be accounted for in the calculation to properly size
the SCR Bus Supply.

Table 1.A Normal Duty ND (110%, 1 minute; 150%, 3 seconds)

Table 1.B Heavy Duty HD (150%, 1 minute; 200%, 3 seconds)

Drive Rating

Drive Output Current

Drive DC Input Current

SCR Bus Supply

(1)

DC
Voltage

ND
Power

ND Output
Currents

ND Output
Current Sum

ND DC Input
Currents

ND DC Input
Current Sum

Maximum DC
Output Amps

AC Input
Voltage

540V

3 x 110 kW
1 x 45 kW

3 x 205 = 615A
1 x 85 = 85A

700A

3 x 226 = 678A
1 x 95 = 95A

773A

1000A

400V

650V

3 x 60 HP
1 x 30 HP

3 x 77 = 231A
1 x 40 = 40A

271A

3 x 84.5 = 253.5A
1 x 42.9 = 42.9A

297A

400A 480V

(1)

No overload capability.

Drive Rating

Drive Output Current

Drive DC Input Current

SCR Bus Supply

(1)

DC
Voltage

HD
Power

HD Output
Currents

HD Output
Current Sum

HD DC Input
Currents

HD DC Input
Current Sum

Maximum DC
Output Amps

AC Input
Voltage

540V

3 x 90 kW

3 x 170 = 510A 510A

3 x 192.3 = 577A

577A

600A

400V

(1)

No overload capability.