Specifications

A-3

PowerFlex SCR Bus Supply User Manual

Publication 20S-UM001G-EN-P

Bus Supply Dimensions

The overall dimensions and mounting holes of the PowerFlex SCR Bus
Supply are shown in

Figure A.1

. Connection Bus Bar dimensions

are shown

in

Figure A.2

,

Figure A.3

, and

Figure A.4

.

Figure A.1

Bus Supply Mounting Dimensions

Environment
(continued)

Shock:

15G peak for 11 ms duration (± 1.0 ms)

Vibration:

0.152 mm (0.006 in.) displacement, 1G peak

Atmosphere:

Important: The bus supply must not be installed in an area
where the ambient atmosphere contains volatile or corrosive
gas, vapors or dust. If the bus supply is not going to be installed
for a period of time, it must be stored in an area where it will not
be exposed to a corrosive atmosphere.

Surrounding Environment:

The fan has a L10 rated life of 74,000 hours in a clean
environment. Execessive dust and heat will degrade fan life.

Permitted
Maximum
Capacitance

Maximum Capacitance for Connection
to the DC Bus Supply

This is the total DC Bus capacitance sum of the permitted
drives to connect. See

Minimum Capacitance on page 1-6

and

Jumper Settings on page 1-12

.

Category

Specification

SCR Bus
Supply

Dimensions

Weight

A

B

C

D

E

400A

535 (21.1)

404 (15.9)

580 (22.8)

276 (10.9)

138.5 (5.5)

30

kg

(66 lb.)

600A

740 (29.1)

490 (19.3)

785 (30.9)

276 (10.9)

104.5 (4.1)

43 kg (95 lb.)

1000A

740 (29.1)

490 (19.3)

785 (30.9)

276 (10.9)

104.5 (4.1)

67 kg (147 lb.)

200 (7.87)

30 (1.2)

Ø 9.5 (0.37)

Not provided

on 400A Units

Ø 35 (1.4) Holes
for Lifting Hooks

Dimensions are in millimeters and (inches).

9.5
(0.37)

29

(1.14)

339.5

(13.4)

B

E

C

D

A

17 x 5 (0.67 x 0.2)
Slots for Precharge
Board LEDs

Side View

Front View