• Conformity of the drive with CE EMC requirements does not guarantee

an entire machine installation complies with CE EMC requirements.
Many factors can influence total machine/installation compliance.

Essential Requirements for CE Compliance

Conditions 1…5 listed below must be satisfied for the PowerFlex SCR Bus
Supply to meet the requirements of EN61800-3.

1. Bus Supply and inverter must be PowerFlex type and CE compatible.

2. Externally mounted Line Reactor and HF filter (specified in

Appendix A

) must be connected to the line input as shown in

Figure 1.8 on page 1-12

.

3. Review important precaution/attention statements throughout this

document before installing the drive(s).

4. Grounding as described in

General Grounding Requirements on

page 1-5

.

5. Control wiring and DC bus wiring leaving the cabinet must be braided,

shielded cable with a coverage of 75% or better, metal conduit or
equivalent attenuation.

For additional conditions, refer to the respective drive Reference Manual.