Control Wiring

Important points to remember about control wiring:

• Use Copper wire only. Wire gauge requirements and recommendations

are based on 75 °C (168 °F). Do not reduce wire gauge when using
higher temperature wire.

• Wire with an insulation rating of 600V or greater is recommended.

• Control wires outside the cabinet

should be separated from power wires

by at least 0.3 meters (1 foot).

Table 1.F Control Terminal Specifications

Figure 1.7

Control Terminal Arrangement

Item Name

Wire Size Range

(1)

(1)

Maximum/minimum sizes that the terminals will accept - these are not
recommendations.

Torque

Maximum

Minimum

Control Terminals

2.5 mm

2

(14 AWG)

0.25 mm

2

(22 AWG)

0.8 N•m
(7 lb•in)

Terminal

Bus Supply

Description

Notes

115 and 0

All units

115V AC
Supply Input

For cooling blower (and power supply on the
Gate Driver Board - on Master and Slave Units)

1 and 2

(1)

(1)

Not used on Slave Units.

Contactor Coil
115V AC

Contactor must be energized to enable the
controller

4 and 5

(1)

NC Contact
Output

(2)

(2)

Refer to

Appendix A

for contact rating.

Opens if the Enable Contactor is energized

6 and 7

400A and 600A
units

NC Contact
Output

(2)

Opens if any of the snubber circuit fuses
(F6…F8) trip

1000A units

Opens if any of the snubber circuit fuses or DC
bus feedback fuses (F7…F11) trip

8 and 9

400A and 600A
units

NC Contact
Output

(2)

Opens if any of the line input or DC bus branch
circuit fuses (F1…F5) trip

1000A units

Opens if any of the line input branch circuit fuses
(F1…F6) trip

10 and 11

All units

NC Contact
Output

(2)

Opens at power stack heat sink overtemperature

12 and GND

All units

Jumper MOVs
to Ground

Disconnects MOVs from ground by removing this
jumper. (See

Disconnecting MOVs on page 1-14

for details.)