Parallel connection of slave units, Parallel connection of slave units -15 – Rockwell Automation 20G PowerFlex SCR Bus Supply User Manual

Page 29

Advertising
background image

Installation/Wiring

1-15

PowerFlex SCR Bus Supply User Manual

Publication 20S-UM001G-EN-P

Parallel Connection of Slave
Units

Up to four 1000A PowerFlex SCR Bus Supply Slave units may be
connected in parallel with one 1000A Master. The derate for each additional
slave is 5% plus 5% for the master. Thus, the maximum possible output
rating without altitude or ambient derating is 4750 Amps (0.95 x 5 x 1000
amps) at 40 °C.

Figure 1.10 Example for Master-Slave Configuration

(shown without circuit protection for clarity)

DC Bus

Power

Input

Master Unit

Slave Unit #1

Slave Unit #n

Precharge

Board

Enable
Contactor

Gate

Driver

Gate

Driver

Gate

Driver

Cable

Cable

Main Switch or
Main Input Contactor

Up to 5 Units Maximum

(4750A Maximum DC Bus Current

without altitude or ambient derating)

Aux. Supply

115 VAC

Advertising