Drive run interlock, Control wiring example, Jumper settings – Rockwell Automation 20G PowerFlex SCR Bus Supply User Manual

Page 26: Jumper settings -12

Advertising
background image

1-12

Installation/Wiring

PowerFlex SCR Bus Supply User Manual
Publication 20S-UM001G-EN-P

Drive Run Interlock

To protect the Bus Supply from overtemperature, the normally closed
contacts (Bus Supply Overtemperature - terminals 10 and 11) should be
wired to either the AC line input contactor for the Bus Supply or the Run
interlock circuit (enable input) of each connected drive. This ensures that
the drives are stopped in case of Bus Supply Overtemperature.

Control Wiring Example

Figure 1.8

Example of SCR Bus Supply, 1000A Single with Multiple Drives Using
Drive Run Interlocks, Running Simultaneous

Jumper Settings

The PowerFlex SCR Bus Supply precharge board has three jumpers. See

Figure 1.9 on page 1-13

for jumper locations and positions.

• LINE TYPE Jumper: Always set to the “3-ph” default right-side position

(towards the board edge).

• SPARE 1 Jumper: For board firmware version 1.21 (or earlier), this

jumper is non-functional. For firmware version 1.22 (or later), the SCR
Bus Supply is shipped with this jumper in the right (default) inactive
state position. When the jumper is placed in the left (RGU/AFE) or
active position, the firmware is active for SCR and RGU/AFE

parallel

operation on common bus systems, where the SCR is in parallel with an

DC Bus

10

115 VAC

6

8

9

11

7

2

1

f

4

5

PowerFlex

SCR Bus

Supply

F7-11

F7-F9

F1-F6

F1-6

L1

K1M

K1M

K1M

K1M

K1M

K1M

K1M

Run

Stop

K1 *

M

0

*

115

* The customer’s controls
must, at a minimum,
command the blower
to run whenever contactor
K1 is enabled.

RC

-

f

-

f

-

f

-

AC Drive

110 kW

205A

AC Drive

110 kW

205A

AC Drive

110 kW

205A

AC Drive

45 kW

85A

f

M

Precharge

Board

>°C

3

M

3

M

3

M

3

NOTE: Optional HF Filter
(see

page A-11

)

Advertising