A-10, Table a.d – Rockwell Automation 20G PowerFlex SCR Bus Supply User Manual

Page 52

Advertising
background image

A-10

Specifications

PowerFlex SCR Bus Supply User Manual
Publication 20S-UM001G-EN-P

Table A.D 690V, 50Hz Line Reactor Selection

Drives

Ranges of Drives DC Amp Sum for Typical Supply Transformers

(1)

Line Reactor

Sum of
DC Amps

630 kVA
5%
123

µ

H

800 kVA
5%
95

µ

H

1000 kVA
5.5%
86

µ

H

1250 kVA
6%
75

µ

H

1600 kVA
6%
59

µ

H

2500 kVA
6.5%
42

µ

H

3000 kVA
6.5%
33

µ

H

Induct.
[

µ

H]

Catalog No.
1321-

(2)

up to 203

130-150

130-157

130-162

130-170

140-180

150-185

2x150 3R160-B

(3)

130-175

151-190

158-203

163-203

171--203

181-203

186-203

230

3R160-C

176-203

191-203

150

3R160-B

75

3R160-A

204 to 255

204-210

204-220

2x110 3R200-B

(3)

204-206

204-230

204-245

204-255

204-255

211-255

221-255

185

3R200-C

207-255

231-255

246-255

110

3R200-B

55

3R200-A

256 to 319

256-260

2x90

3RB250-B

(3)

256-260

256-270

256-290

256-319

256-319

261-319

150

3RB250-C

256-280

261-319

271-319

291-319

90

3RB250-B

281-319

45

3RB250-A

320 to 407

320-360

320-407

320-407

125

3RB320-C

320-360

320-380

320-407

361-407

75

3RB320-B

320-407

361-407

381-407

40

3RB320-A

408 to 509

408-465

408-509

105

3RB400-C

408-414

408-450

408-509

466-509

60

3RB400-B

408-500

415-509

451-509

30

3RB400-A

510 to 635

510-520

510-580

85

3R500-C

510-538

510-570

521-635

581-635

50

3R500-B

510-540

539-635

571-635

25

3R500-A

636 to 763

636-650

65

3R600-C

636-763

651-763

40

3R600-B

661-763

20

3R600-A

764 to 938

764-780

48

3R750-C

764-850

781-938

29

3R750-B

851-938

15

3R750-A

939 to 1K0

42

3R850-C

939-1K0

939-1K0

27

3R850-B

15

3R850-A

(1)

The inductance value of the supply transformers includes 2.5 µH for 10 m feeder cable.

(2)

The number in the catalog string represents the fundamental AC current of the reactor.

(3)

Connect two reactors in series.