Scr bus supply 12-pulse configuration, Scr bus supply 12-pulse configuration -18 – Rockwell Automation 20G PowerFlex SCR Bus Supply User Manual

Page 32

Advertising
background image

1-18

Installation/Wiring

PowerFlex SCR Bus Supply User Manual
Publication 20S-UM001G-EN-P

SCR Bus Supply 12-Pulse
Configuration

Standalone or master/slave SCR Bus Supplies can be used on applications
that use a 12-pulse transformer to minimize power line harmonics.

Important: Be sure to select the slow ramp time

(see

Jumper Settings on

page 1-12

).

Figure 1.12

shows a recommended 12-pulse system configuration with

optional slave SCR Bus Supplies.

Figure 1.12 12-Pulse System Configuration

For additional recommendations about SCR Bus Supply 12-pulse
configurations, contact Rockwell Automation Technical Support.

Y

Reactor

Standalone

or

Master

SCR Bus

Supply

Reactor

Fuses*

Gate

Harness

Fuses*

Enable

Slave

Reactor

12-Pulse
Transformer

Slave

Reactor

AC Line

Standalone

or

Master

SCR Bus

Supply

Gate

Harness

Fuses*

Fuses*

* Fuses are optional.