Troubleshooting

Table 2.B Possible Faults and Corrective Actions

Fault

Cause

Corrective Action

Heat sink
Overtemperature

Heat sink temperature
exceeds maximum rating

1. Verify that maximum ambient temperature has

not been exceeded.

2. Check Overtemperature Switch (N.C. contacts)

at control terminals 10 and 11.

3. Check 115V AC supply input voltage at control

terminals 0 and 115.

4. Check blower for correct operation.

5. Check for excess load on the bus supply.

6. Check for minimum mounting clearance around

the bus supply.

7. Contact your local RA sales office.

DC Output
Voltage Loss

DC bus:

- Short Circuit FAULT [2] or
- Low Line

FAULT [4] or

- No Load

ALARM [7]

Refer to

Table 2.A

.

1. Check 3-phase AC incoming power for

undervoltage or phase loss.

2. Check all Bus Supply fuse trip indicator switches.

3. Verify the Inverter is connected.

4. Verify the power of the connected Inverter(s) is

minimum 7.5 kW (10 HP). Refer to the 2nd
Attention statement on

page 2-1

.

5. Contact your local RA sales office.

Loss of 115V AC power

1. Check 115V AC supply input voltage at control

terminals 0 and 115.

2. Check Enable Contactor function.

3. Contact your local RA sales office.

Jumper setting
wrong

Wrong jumper settings:

Single phase (1-ph) line
type and one or both of the
SPARE 1 or SPARE 2
jumpers set to their
respective left positions.

1. Check the jumper setting(s).

2. Set the jumper(s) correctly.