Start Up/Troubleshooting

2-5

PowerFlex SCR Bus Supply User Manual

Publication 20S-UM001G-EN-P

Table 2.A Precharge Board LED Indicators

Figure 2.2

Flashing Pattern for ALARM and FAULT LEDs

Example: Flashing pattern for ALARM LED showing a Low Phase alarm (where n = 3 flashes)

Name

Color

State

Description

POWER OK

Green

Steady

Illuminates when precharge board power supply is operational.

ALARM

Yellow

Flashing

The number [n] of flashes (see flashing pattern in

Figure 2.2

)

indicates one of the following alarms

(1)

:

(1)

The ALARM indicator LED will continue the flashing pattern as long as the alarm condition exists. An alarm
might trigger internal actions which may stop SCR gate firing.

[1]

[2]

[3]

[4]

[5]

[6]

[7]

Low Line Voltage (< 90%)
Low Line Voltage (< 65%) for SCR and RGU/AFE paralleling
mode

Very Low Line Voltage (< 50%)

Low Phase (One phase < 80% of line voltage), or
Low Phase Voltage (One phase < 56% of line voltage) for SCR
and RGU/AFE paralleling mode

Freq. out of range or asymmetry (Line synchronization failed)

Low DC Bus Voltage (triggers ride-through operation)

Input Frequency momentarily out of range (40…65 Hz)

DC Bus Short Circuit testing active (repetitive for appr. 120 s) or
no inverter connected to the bus

FAULT

Red

Flashing

The number [n] of flashes (see flashing pattern in

Figure 2.2

)

indicates one of the following faults

(2)

:

(2)

If a fault occurs, the FAULT indicator LED will continue the flashing pattern, even if the fault condition no longer
exists. Power must be cycled to clear the fault.

[2]

[4]

[5]

DC Bus Short (Udc < 2% after 20ms)

Line Synchronization failed or Low Line (Uac < 50% Unom)

Jumper setting wrong

Pause

0.3

sec.

0.3

sec.

0.9 sec.