Accessories, Line reactors – Rockwell Automation 20G PowerFlex SCR Bus Supply User Manual

Page 49

Advertising
background image

Specifications

A-7

PowerFlex SCR Bus Supply User Manual

Publication 20S-UM001G-EN-P

Accessories

Line Reactors

A minimum reactance is required to limit peak currents in the AC line and
the bridge circuit. This can be accomplished either by a matched supply
transformer or by adding line reactors to ensure the requested minimum
voltage drop over the total line impedance. The preferred method is to
install a minimum 3% line reactor, which will also reduce line harmonics.

Use

Table A.A

through

Table A.D

to select a line reactor based on the sum

of the drive’s connected DC Amps and the supply transformer rating.

For more details on the 1321-Series line reactors, see the 1321 Power
Conditioning Products Technical Data
(publication 1321-TD001).

Table A.A 400V, 50Hz Line Reactor Selection

Drives

Ranges of Drives DC Amp Sum for Typical Supply Transformers

(1)

Line Reactor

Sum of
DC Amps

630 kVA
5%
43

µ

H

800 kVA
5%
35

µ

H

1000 kVA
5.5%
31

µ

H

1250 kVA
6%
27

µ

H

1600 kVA
6%
22

µ

H

2500 kVA
6.5%
16

µ

H

3000 kVA
6.5%
13

µ

H

Induct.
[

µ

H]

Catalog No.
1321-

(2)

up to 203

120-150

120-154

120-160

120-165

120-168

120-173

120-176

230

3R160-C

151-203

155-203

161-203

166-203

169-203

174-203

177-203

150

3R160-B

75

3R160-A

204 to 255

204-206

204-209

204-219

204-224

185

3R200-C

204-255

204-255

204-255

207-255

210-255

220-255

225-255

110

3R200-B

55

3R200-A

256 to 319

256-260

256-275

150

3RB250-C

256-319

256-319

256-319

256-319

256-319

261-319

276-319

90

3RB250-B

45

3RB250-A

320 to 407

125

3RB320-C

320-335

320-370

320-390

320-407

320-407

320-407

320-407

75

3RB320-B

336-407

371-407

391-407

40

3RB320-A

408 to 509

105

3RB400-C

408-425

408-450

408-480

408-509

408-509

408-509

60

3RB400-B

408-509

426-509

451-509

481-509

30

3RB400-A

510 to 635

510-538

510-590

510-635

510-635

50

3R500-B

510-540

510-580

510-635

539-635

591-635

25

3R500-A

636 to 763

636-660

636-763

636-763

40

3R600-B

636-763

636-763

636-763

661-763

20

3R600-A

764 to 938

764-900

764-938

29

3R750-B

764-800

764-870

764-900

764-938

901-938

15

3R750-A

939 to 1K0

939-1K0

939-1K0

27

3R850-B

939-1K0

15

3R850-A

(1)

The inductance value of the supply transformers includes 2.5 µH for 10 m feeder cable.

(2)

The number in the catalog string represents the fundamental AC current rating of the reactor.

Advertising