Rockwell Automation 20G PowerFlex SCR Bus Supply User Manual

Page 27

Advertising
background image

Installation/Wiring

1-13

PowerFlex SCR Bus Supply User Manual

Publication 20S-UM001G-EN-P

active front end that is used only as a regenerative brake unit. The
PowerFlex SCR Bus Supply will then deliver the required motoring
power and the RGU/AFE will provide the possibility to feed the
regenerative energy back to the AC power line.

The auto-voltage

limitation (allowing the SCRs to phase back) associated with high AC
line will be disabled. The left (RGU/AFE) jumper position provides the
best protection for parellel SCR and RGU/AFE operation.

• SPARE 2 Jumper: For board firmware version 1.21 (or earlier), this

jumper is non-functional. For firmware version 1.22 (or later), this
jumper is used for slow ramp-up, which slows the DC bus voltage charge
up time (from 0.2 to 1.3 seconds). Slow ramp-up should be used when
the connected DC bus capacitance is greater than the values shown in the
following table.

To operate the SCR Bus Supply with a slow ramp-up, set the SPARE 2
jumper to the left (SLOW) position.

For standard applications where only the PowerFlex SCR Bus Supply
provides the required common DC power, make sure the SPARE 1 and
SPARE 2 jumpers are in their default settings (right side—towards the
board edge) shown in

Figure 1.9

.

Figure 1.9

Location of LED Indicators and Jumpers on the Precharge Board

SCR Bus Supply

Max. Bus Capacitance

(1)

with Normal Ramp

(1)

It is recommended to derate the capacitance value by 20% in master/slave configurations.

Max. Bus Capacitance

(1)

with Slow Ramp

400A

40,000 µF

200,000 µF

600A

60,000 µF

300,000 µF

1000A @ 480V

100,000 µF

500,000 µF

1000A @ 690V

50,000 µF

250,000 µF

SPARE

2

(Ramp-Up)

Precharge Board
Firmware Version Label

(SCR and
RGU/AFE

Paralleling)

Slow Norm

Yes No

1-ph 3-ph

SPARE

1

LINE

TYPE

POWER

OK

ALARM

LEDs

Jumpers sho

wn in

def

ault positions

FAULT

TIP: To identify the firmware version, remove the SCR Bus Supply cover
and check the firmware version label on the Precharge Board (

Figure 1.9

).