Start-Up

Before Applying Power to the Bus Supply

1. Verify that the minimum of one Inverter is connected to the DC bus.

2. Confirm that all inputs are connected to the correct terminals and are

properly torqued.

3. Using an ohmmeter or other continuity testing device, verify that shorts

do not exist between Source 1 and Source 2:

4. Verify that AC line power at the disconnect device is within the rated

value of the Bus Supply. See

Appendix A

.

5. Verify that control power voltage is correct.

6. Verify that the enable contactor coil K1 (not used on Slave units) is

correctly wired.

7. Verify that these four outputs are correctly wired:

Bus Supply Overtemperature
Rectifier Fuse Trip
Snubber/DC feedback Fuse Trip
Enable Contactor Feedback (not used on Slave units)

These normally closed contact outputs are used to set alarms and to stop
the drive(s). Verify that they have been wired correctly according to the
user’s specification. Refer to the control wiring example shown in

Figure 1.8 on page 1-12

.

8. Verify that the “Line Type” jumper on the Precharge Board shown in

Figure 2.1

is set to the “3-ph” position (default).

Source 1

Source 2

Checkmark Below if No Short Exists

L1

L2

L1

L3

L2

L3

L1

PE

L2

PE

L3

PE

L1

DC+ Bus

L2

DC+ Bus

L3

DC+ Bus

L1

DC- Bus

L2

DC- Bus

L3

DC- Bus

DC+ Bus

DC- Bus

DC+ Bus

PE

DC Bus

PE