Start Up/Troubleshooting

2-7

PowerFlex SCR Bus Supply User Manual

Publication 20S-UM001G-EN-P

Important: Complete the tests listed in

Table 2.C

without power applied to

the SCR Bus Supply.

Table 2.C Control Terminal Block Continuity Test Conditions

Test Condition

Possible Cause

Corrective Action

N.C. contact on
control terminals
6 and 7 is open

400A and 600A Unit: Open
snubber fuse (F6…F8).

1000A Unit: Open snubber
fuse or open DC bus fuse
(F7…F11).

1. Check for evidence of power module failure (see

Step 3 in

Start-Up on page 2-2

).

2. Check for evidence of failure in snubber circuit.

Check the snubber pcb diodes and snubber
resistor and capacitor.

3. Replace entire SCR Bus Supply if any device

has failed.

4. If there is no evidence of a failure, check for open

fuse and replace.

N.C. contact on
control terminals
8 and 9 is open

400A and 600A Unit: Open
AC line fuse or open DC bus
fuse (F1…F5).

1000A Unit: Open AC line
fuse (F1…F6).

1. Check for evidence of power module failure (see

Step 3 in

Start-Up on page 2-2

).

2. Replace entire SCR Bus Supply if any device

has failed.

3. If there is no evidence of power module failure,

check for open fuse and replace.

N.C. contact on
control terminals
10 and 11 is open

Open heat sink
Overtemperature Switch

1. Verify that maximum ambient temperature is not

exceeded.

2. Replace the Overtemperature Switch.