Waveform data records – Rockwell Automation 1426 PowerMonitor 5000 Unit User Manual
Page 107

Rockwell Automation Publication 1426-UM001F-EN-P - November 2013
107
Logging
Chapter 6
Waveform Data Records
The LoggingResults.Waveform_Log table contains the most recent record read
from the selected waveform file, and contains the following REAL elements.
Element Number
Tag Name
Description
0
Record_Indicator
Indicates the significance of the data in the record
0 = No record returned
1 = the record contains parameter values
2 = the record contains general information of the log file being retrieved, reference to each item
description in the data table;
3 = log file not found.
1
Timestamp_Date
Date of cycle collection MMDDYY
2
Timestamp_Time
Time of cycle collection hhmmss
3
Microsecond_Stamp
Microsecond of cycle collection
4
File_ID
The selected file ID
5
Total_Cycles
Total cycles of the waveform file
6
Cycle_Returned
The current returned cycles
7
Frequency
The frequency of average cycle
8
Mag_Angle
The returned value is magnitude or angle
9
Channel
The channel returned
10
Order
The order of returned values
11
X_(0 + Order * 32)
The returned value X_(h) where X_(h) = the RMS magnitude or angle of the spectral component h. Units are
Volts, Amps or degrees, depending on the value of Channel and Mag_Angle elements
12
X_(1 + Order * 32)
…
…
42
X_(31 + Order * 32)