Rockwell Automation 1426 PowerMonitor 5000 Unit User Manual
Page 56

56
Rockwell Automation Publication 1426-UM001F-EN-P - November 2013
Chapter 4
Metering
RangeN_Voltage_Input_Inverted
RangeN_Current_Input_Inverted
These are the values:
-1 = Test not run
0 = Test passed
1 = Phase 1 inverted
2 = Phase 2 inverted
3 = Phase 3 inverted
12 = Phase 1 and 2 inverted
13 = Phase 1 and 3 inverted
23 = Phase 2 and 3 inverted
123 = All phases inverted
Voltage_Rotation
Current_Rotation
These are the values:
123…321 designating phase and rotation. Example: 213 = Phase 2 then
phase 1 then phase 3
-1 = Test not run
4 = Invalid Rotation
5 = Out of range
Phasor Magnitudes and Angles
The PowerMonitor 5000 unit updates these values continually.
Voltage_Phase_1_Angle (always zero)
Voltage_Phase_1_Magnitude
Voltage_Phase_2_Angle
Voltage_Phase_2_Magnitude
Voltage_Phase_3_Angle
Voltage_Phase_3_Magnitude
Current_Phase_1_Angle
Current_Phase_1_Magnitude
Current_Phase_2_Angle
Current_Phase_2_Magnitude
Current_Phase_3_Angle
Current_Phase_3_Magnitude